THHN / THWN Nylon-Jacketed Wires
600 V — up to 105°C

THHN / THWN Nylon-Jacketed Wires

TFFN, THHN and THWN wires are designed for special-purpose applications requiring high heat and water resistance, with a maximum operating temperature of 105°C. The stranded conductor complies with SASO GSO IEC TR 62602. The insulation is a special heat-resistant PVC compound rated 105°C, and a nylon jacket is extruded tightly over the insulation for extra mechanical protection.

  • Special heat-resistant PVC insulation rated 105°C.
  • Tough nylon jacket extruded tightly over the insulation.
  • Stranded copper conductor to SASO GSO IEC TR 62602.
  • Ideal for high-heat, damp and special-purpose locations.

Technical Specifications

Relevant Standard SASO IEC 60227-3 — CU/PVC/NYLON
Conductor Material Plain annealed copper, Class 2 (SASO GSO IEC TR 62602)
Insulation PVC 105°C + nylon jacket
Colour Code Red, Yellow, Blue, Black, Grey, Brown or as per customer request
Temperature Range Up to 105°C
Conductor Resistance According to GSO IEC TR 62602
Rated Voltage 600 V
Test Voltage As per IEC 60227-3 — 2 kV
Packing Wooden drums or spools

Need this product for your project?

Contact our sales team for sizes, colours, lengths and pricing.

Get a Quote

Back to all products

Product Data

Standard Sizes

AWG size Cross-section (mm²) Max. DC resistance @20°C (Ω/km) PVC insulation, average thickness (mm) Nylon jacket, minimum thickness (mm) Overall diameter, approx. (mm) Cable weight, approx. (kg/km)
14 1 × 2.08 8.62 0.38 0.10 3.15 25
12 1 × 3.31 5.43 0.38 0.10 3.70 38
10 1 × 5.26 3.41 0.51 0.10 4.60 60
8 1 × 8.37 2.14 0.76 0.13 6.00 97
6 1 × 13.3 1.35 0.76 0.13 7.00 150

Diameters and weights are approximate values.

Correction factor for ambient temperature

Ambient temperature 25°C35°C40°C45°C50°C55°C60°C70°C80°C
Correction factor 1.030.970.930.890.860.820.770.680.58

Full catalogue (PDF)